Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No a copy of the state operating certificate shall be posted in the disconnect room 3/3/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.8 - Top emergency exit 8.11.2.1.3(l) No No Need wing bolt instead of hex head bolt -WC
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 No No Provide maintenance and call back logs, fill out monthly fire service test logs last done in 2023 -WC
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.11.1 Firefighters’ Emergency Operation Documentation No No need to have a monthly fire service test log posted in the disconnect room 3/3/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 4.5 - Access to Hoistway 8.6.4.14 Hoistway Access Switches Yes No Top and bottom landing hoistway access key switch did not function -RI required
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.5 - Car lighting and receptacles 8.6.4.15 Emergency Lighting Yes No Emergency lights did not come on -RI required
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.5 - Housekeeping 8.6.4.8 Machine Rooms and Machinery Spaces No No Do not store non elevator related items in the elevator disconnect room 5/9/2024