A17.1-2016 : Elevators
|
3.10 - Hoistway construction
|
8.7.2.1.1 Hoistway Enclosure Walls
|
x
|
|
Seal all penetrations in the hoistway.
|
6/15/2022
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.4 Instructions for Locating Maintenance Records
|
x
|
|
A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room.
|
6/15/2022
|
A17.1-2016 : Elevators
|
2.7 - Fire Extinguisher
|
8.10.2.2.2(l)
|
x
|
|
An ABC type fire extinguisher shall be mounted at the 7th floor near the elevator door as the controller is located in the jamb at the 7th floor.
|
6/15/2022
|
A17.1-2016 : Elevators
|
1.15 - sign and operating device symbols
|
8.10.2.2.1(o)
|
x
|
|
Install all signage.
|
6/15/2022
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
8.10.2.2.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
The in car emergency telephone shall be operational.
|
6/15/2022
|
A17.1-2016 : Elevators
|
1.4 - Sills and car floor
|
8.10.2.2.1(d)
|
x
|
|
The cab flooring shall be installed.
|
6/15/2022
|
A17.1-2016 : Elevators
|
1.3 - Operating control devices
|
8.10.2.2.1(c)
|
x
|
|
Finish all hallway walls and install install hallway fixture.
|
6/15/2022
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Post current state operating certificate onsite
|
10/26/2023
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.2 through 2.27.8 Firefighter Service
|
x
|
x
|
All phases of fire service and all fire service initiating devices shall be tested.
|
6/15/2022
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.2.6 Sump Pump Covers
|
x
|
|
The sump pump shall have a cover installed.
|
6/15/2022
|