MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6 General Maintenance Methods
|
|
|
The suspension rope retainer on the drive sheave is rubbing the hoist ropes. Adjust for proper clearance.
|
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.2.2 On-Site Documentation
|
|
|
A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room.
|
|
A17.1-2016 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
2.27.1.1.1 Emergency communications and alarm not functioning (Red Tag)
|
x
|
|
The in car emergency telephone shall be operational.
|
11/25/2020
|
A17.1-2016 : Elevators
|
3.12 - Pipes, wiring, and ducts
|
8.10.2.2.3(r)
|
x
|
|
Install hoistway and car top duct covers.
|
11/25/2020
|
A17.1-2016 : Elevators
|
2.11 - Disconnecting Means and Control
|
8.10.2.2.2(r)
|
x
|
|
The electrical disconnects shall be labeled with the location, name, and breaker numbers of the panel from which it is fed.
|
11/25/2020
|
A17.1-2016 : Elevators
|
3.20 - Governor rope
|
2.18.5
|
x
|
|
Governor rope shall not rub guard.
|
11/25/2020
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.2.2(a) On-Site Documentation (Up-to-Date Wiring Diagrams)
|
x
|
|
Provide code compliant onsite documents.
|
11/25/2020
|
A17.1-2016 : Elevators
|
2.7 - Fire Extinguisher
|
8.6.1.6.5
|
x
|
|
Provide a code compliant fire extinguisher near the machine space.
|
11/25/2020
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.3
|
x
|
x
|
Test Phases 1 & 2 fire service and all fire service initiating devices.
|
11/25/2020
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.9 Elevator Corridor Call Station Pictograph
|
x
|
|
Provide "In Case of Fire" signage.
|
11/25/2020
|
A17.1-2016 : Elevators
|
3.13 - Windows, projections, recesses, and setbacks
|
2.11.10.1
|
x
|
|
2.11.10.1.1 - Provide landing sill guards.
|
11/25/2020
|
A17.1-2016 : Elevators
|
2.14 - Code data plate
|
8.10.2.2.2(ll)
|
x
|
|
8.10.1.1.4 - Provide acceptance test tags.
|
11/25/2020
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
2.27.2
|
x
|
|
Battery lowering shall be operational.
|
11/25/2020
|