Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 2.14 - Code data plate 8.10.2.2.2(ll) x 8.10.1.1.4 - Provide acceptance test tags. 11/25/2020
A17.1-2016 : Elevators 1.17 - Standby power operation 2.27.2 x Battery lowering shall be operational. 11/25/2020
A17.1-2016 : Elevators 3.12 - Pipes, wiring, and ducts 8.10.2.2.3(r) x Install hoistway and car top duct covers. 11/25/2020
A17.1-2016 : Elevators 2.11 - Disconnecting Means and Control 8.10.2.2.2(r) x The electrical disconnects shall be labeled with the location, name, and breaker numbers of the panel from which it is fed. 11/25/2020
A17.1-2016 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 x Provide a code compliant fire extinguisher near the machine space. 11/25/2020
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3 x x Test Phases 1 & 2 fire service and all fire service initiating devices. 11/25/2020
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.9 Elevator Corridor Call Station Pictograph x Provide "In Case of Fire" signage. 11/25/2020
A17.1-2016 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room.