Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.1.1 Phase I Emergency Recall Operation x x Fire recall programming not completed. Complete and retest. 11/12/2020
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.11.2.1.5(a) x Increase pit illumination to 10 ft candles throughout measured at the pit floor. 11/12/2020