Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 3.10 - Hoistway construction 2.1 Yes No Seal penetrations in hoistway wall. 11/20/2020
A17.1-2016 : Elevators 2.7 - Fire Extinguisher 8.10.2.2.2(l) Yes No Provide type ABC fire extinguisher in close proximity to machine space. 11/20/2020
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.2 Phase I Operation Recall by Initiating Device Yes Yes Provide testing of phase 1 operation by initiating devices. 11/20/2020
A17.1-2016 : Elevators 1.17 - Standby power operation 8.10.2.2.1(q) Yes No Provide testing of emergency power operation with 125% of rated loaad. 11/20/2020
A17.1-2016 : Elevators 1.6 - Car emergency signal 2.27.1.1.6 Verification of Telephone Operability Yes No Provide means to verify telephone operability. Elevator phone line monitoring equipment has not been installed. 11/20/2020
A17.1-2016 : Elevators 1.6 - Car emergency signal 2.27.1.1.1 Emergency communications and alarm not functioning (Red Tag) Yes No Provide means for two way conversation inside elevator. Phone is inoperative. 11/20/2020
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.8 Switch Keys Yes No Provide access to firefighter operation key on site for firefighters and emergency personnel. 11/20/2020
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.9 Elevator Corridor Call Station Pictograph Yes No Post corridor call station pictograph next to top landing call station. "In case of fire do not use elevator" 11/20/2020
A17.1-2016 : Elevators 3.12 - Pipes, wiring, and ducts 2.8 Yes No Electrical wire in hoistway needs to be in metal conduit. Incoming telephone line, and signal for emergency power are exposed. 11/20/2020