Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Need to complete annual test. Smoke detectors were affected by lighting strike, need to be tested. Re-inspection required 8/2/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.11 - Plunger and Cylinder 3.18 Provide cover(s) on oil collection pans in pit. 9/23/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.11 Periodic Inspection and Test. x The previous inspector indicated that the building was struck by lightning and smoke detectors were affected. Testing of the fire alarm system and the smoke detectors is required. 9/6/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 Provide MCP 9/23/2020