ASME A18.1-2014 : Platform Lifts & Stairway Chairlifts
|
2.7 - Capacity, Speed, and Travel
|
2.7.2
|
|
|
A capacity tag is required to be posted on the platform.
|
|
Missouri Minimum : Platform Lifts
|
(U) - Existing Vertical and Inclined Platform Lifts
|
(U)1 (Re-Inspect)
|
x
|
|
A18.1 - 2.1.6.5 - A pit stop switch is required near the lower level entrance door.
|
6/14/2022
|
Missouri Minimum : Platform Lifts
|
(U) - Existing Vertical and Inclined Platform Lifts
|
(U)1 (Re-Inspect)
|
x
|
|
A18.1 - 2.1.7 - There is a disconnect inside the tower that does not appear to work.
|
6/14/2022
|
ASME A18.1-2014 : Platform Lifts & Stairway Chairlifts
|
2.1 - Runways
|
2.1.1.4
|
|
|
Adjust the lower level interlock so that it is functional when the lower level door closes.
|
|
Missouri Minimum : Platform Lifts
|
(U) - Existing Vertical and Inclined Platform Lifts
|
(U)1
|
|
|
RECOMMENDATION: It is recommended that a warning sign be installed on the interior kitchen door that a wheelchair lift door may open. Note: The lift opens directly into a kitchen entry door.
|
|
ASME A18.1-2014 : Platform Lifts & Stairway Chairlifts
|
2.1 - Runways
|
2.1.1.3
|
|
|
Reduce the opening speed of the lower level hoistway door.
|
|
ASME A18.1-2014 : Platform Lifts & Stairway Chairlifts
|
2.1 - Runways
|
2.1.1.1
|
x
|
|
The interior of the runway enclosure shall present a smooth surface on all sides.
|
1/11/2021
|
ASME A18.1-2014 : Platform Lifts & Stairway Chairlifts
|
2.1 - Runways
|
2.1.1.3
|
x
|
|
The lift side of the landing doors and sill shall present a smooth surface located not closer than 10mm (0.375 in.) nor more than 20mm (0.75 in.) from the access edge of the platform floor.
|
1/11/2021
|
ASME A18.1-2014 : Platform Lifts & Stairway Chairlifts
|
2.10 - Operating Devices and Control Equipment
|
2.10
|
x
|
|
The platform disconnect shall be located in sight of the motor controller.
|
1/11/2021
|