MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection)
|
x
|
|
Emergency light not working. Bulbs?
|
9/19/2024
|
A17.1-2016 : Elevators
|
3.10 - Hoistway construction
|
2.1
|
x
|
|
Exposed wood & roof cap shall have fire rated material added for protection.
|
9/6/2022
|
A17.1-2016 : Elevators
|
3.13 - Windows, projections, recesses, and setbacks
|
2.1.6
|
x
|
|
Set backs in the hoistway greater than 4 inches shall be beveled at an angle not less than 75 deg with the horizontal.
|
9/6/2022
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
2.27.1.1.6 Verification of Telephone Operability
|
x
|
|
Emergency Telephone system has not been established.
|
9/6/2022
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.3.2 Phase I Operation Recall by Initiating Device
|
x
|
x
|
The Phase I Emergency Recall Operation by Fire Alarm Initiating Devices per 2.27.3.2.1(a)(b)(c) is required.
|
9/6/2022
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
8.10.2.2.5(a)
|
x
|
|
Elevator pit electrical work has not been initiated.
|
9/6/2022
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.2.2(b)(2)
|
|
|
Provide on site documentation to include testing procedures.
|
6/22/2023
|
A17.1-2016 : Elevators
|
1.5 - Car lighting and receptacles
|
8.6.4.15 Car Emergency System (Re-Inspection)
|
x
|
|
Repair the emergency lights.
|
6/22/2023
|