Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.10.2.2.5(a) x Elevator pit electrical work has not been initiated. 9/6/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x Emergency light not working. Bulbs? 9/19/2024
A17.1-2016 : Elevators 1.6 - Car emergency signal 2.27.1.1.6 Verification of Telephone Operability x Emergency Telephone system has not been established. 9/6/2022
A17.1-2016 : Elevators 3.10 - Hoistway construction 2.1 x Exposed wood & roof cap shall have fire rated material added for protection. 9/6/2022
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.2(b)(2) Provide on site documentation to include testing procedures. 6/22/2023
A17.1-2016 : Elevators 1.5 - Car lighting and receptacles 8.6.4.15 Car Emergency System (Re-Inspection) x Repair the emergency lights. 6/22/2023
A17.1-2016 : Elevators 3.13 - Windows, projections, recesses, and setbacks 2.1.6 x Set backs in the hoistway greater than 4 inches shall be beveled at an angle not less than 75 deg with the horizontal. 9/6/2022