A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.3.3.7 Phase 2 Operation Panel
|
x
|
|
Phase II keyswitch does not active Phase II when turned to the "ON" position (faulty keyswitch)
|
2/26/2026
|
|
A17.1-2016 : Elevators
|
3.23 - Suspension Means
|
8.6.3.2 (Re-Inspection)
|
x
|
|
Suspension belts need replaced, number of runs exceeds manufacturers life cycle for replacement.
|
2/26/2026
|
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
2.11.1.3 Emergency Phone not workng Alarm Functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Provide existing phone to work.
|
1/15/2025
|
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Phone not working (line is dead)
|
2/26/2026
|