Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (A) - Hoistways (A)16 Replace the missing interlock covers where needed.
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Alarm bell shall work. 4/13/2023
MO Minimum : Elevators (C) - Car Enclosure: Freight (C)6 A permanent capacity plate and a "No Passengers" sign shall be installed.
MO Minimum : Elevators (C) - Car Enclosure: Freight (C)4 The car top shall be completely covered and be able to support a 200 lbs. weight.
MO Minimum : Elevators (F) - Electrical Switches (F)2 x The lower limit switches shall be raised up to the first floor if the lower landing is no longer in use. 8/11/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records Provide a code compliant MCP including onsite documents.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts x Second floor limit switch (floor selector switch) is not working in the UP direction. 4/13/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Alarm bell shall work. 6/26/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts x Second floor limit switch (floor selector switch) is not working in the UP direction. 6/26/2023
MO Minimum : Elevators (H) - Machine Rooms (H)1 All means of access to elevator machine rooms shall be constructed and maintained in a clear and unobstructed manner. Need permanent stairs into machine room.
MO Minimum : Elevators (H) - Machine Rooms (H)2 The machine room door shall be self-closing and self-locking.
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) A permanent light fixture shall be installed in the pit with the switch adjacent to the bottom floor door.
MO Minimum : Elevators (I) - Pits (I)8 Provide a permanent, non-combustible pit sump pump cover.
MO Minimum : Elevators (I) - Pits (I)7 x Install emergency stop switch in pit.
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Entirety of the annual testing shall be completed. Testing stopped due to red tag.
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x x Unit red tagged due to car being able to run with car gate and/or hoistway doors open.
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x The elevator enclosure shall be extended to the top of the cab. The area that passes the counterweight shall be solid material. 8/11/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x x The SOS is not operating. Elevator Red Tagged. 4/13/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x Replace all broken slats on front & rear gates. 8/11/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x Provide a permanent pit stop switch adjacent to the pit door. 8/11/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x The car stop switch shall be operational. 8/11/2022