MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4.1(a) On-Site Maintenance Records (MCP Records)
|
|
|
A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room.
|
|
MO Minimum : Elevators
|
(C) - Car Enclosure: Freight
|
(C)6
|
|
|
A permanent capacity plate and a "No Passengers" sign shall be installed.
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)6 (Pit Lighting)
|
|
|
A permanent light fixture shall be installed in the pit with the switch adjacent to the bottom floor door.
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)1
|
|
|
All means of access to elevator machine rooms shall be constructed and maintained in a clear and unobstructed manner. Need permanent stairs into machine room.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
Provide a code compliant MCP including onsite documents.
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)8
|
|
|
Provide a permanent, non-combustible pit sump pump cover.
|
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)16
|
|
|
Replace the missing interlock covers where needed.
|
|
MO Minimum : Elevators
|
(C) - Car Enclosure: Freight
|
(C)4
|
|
|
The car top shall be completely covered and be able to support a 200 lbs. weight.
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
The machine room door shall be self-closing and self-locking.
|
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Alarm bell shall work.
|
4/13/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
Alarm bell shall work.
|
6/26/2023
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Entirety of the annual testing shall be completed. Testing stopped due to red tag.
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)7
|
x
|
|
Install emergency stop switch in pit.
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(1) Minimum Standard
|
x
|
|
Provide a permanent pit stop switch adjacent to the pit door.
|
8/11/2022
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(1) Minimum Standard
|
x
|
|
Replace all broken slats on front & rear gates.
|
8/11/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.3.1 Replacement Parts
|
x
|
|
Second floor limit switch (floor selector switch) is not working in the UP direction.
|
6/26/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.2.1 Repair Parts
|
x
|
|
Second floor limit switch (floor selector switch) is not working in the UP direction.
|
4/13/2023
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(1) Minimum Standard
|
x
|
|
The car stop switch shall be operational.
|
8/11/2022
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(1) Minimum Standard
|
x
|
|
The elevator enclosure shall be extended to the top of the cab. The area that passes the counterweight shall be solid material.
|
8/11/2022
|
MO Minimum : Elevators
|
(F) - Electrical Switches
|
(F)2
|
x
|
|
The lower limit switches shall be raised up to the first floor if the lower landing is no longer in use.
|
8/11/2022
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(1) Minimum Standard
|
x
|
x
|
The SOS is not operating. Elevator Red Tagged.
|
4/13/2023
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(1) Minimum Standard
|
x
|
x
|
Unit red tagged due to car being able to run with car gate and/or hoistway doors open.
|
|