                        A17.1-2016 : Elevators
                     | 
                    
                        2.1 - Access to machine space
                     | 
                    
                        8.11.2.1.2(b)
                     | 
                    
                     | 
                    
                     | 
                    
                        Profide safe access to overhead govenor installation, current vertical ladder in excess of 20ft with access door extending over ladder while opening. a plate form must be provided to stand on while opening door.  Access must be OSHA compliant, door must be marked "danger elevator hoistway"
                     | 
                    
                        4/1/2021
                     | 
                
                
                    | 
                        A17.1-2016 : Elevators
                     | 
                    
                        2.3 - Lighting and receptacles
                     | 
                    
                        8.11.2.1.2(f)
                     | 
                    
                     | 
                    
                     | 
                    
                        A remote stop switch and a light should be installed at overhead govenor which is a remote work space to provide a safe working environment
                     | 
                    
                        4/1/2021
                     | 
                
                
                    | 
                        A17.1-2016 : Elevators
                     | 
                    
                        2.3 - Lighting and receptacles
                     | 
                    
                        8.11.2.1.2(f)
                     | 
                    
                     | 
                    
                     | 
                    
                        A remote stop switch should be installed in overhead when governor is located
                     | 
                    
                        
                     | 
                
                
                    | 
                        A17.1-2016 : Elevators
                     | 
                    
                        2.3 - Lighting and receptacles
                     | 
                    
                        8.11.2.1.2(f)
                     | 
                    
                     | 
                    
                     | 
                    
                        Provide lighting in governor overhead which is a remote work space tp provide a safe working enviroment
                     | 
                    
                        
                     | 
                
                
                    | 
                        MO Minimum : Elevators
                     | 
                    
                        (G) - Maintenance, Repair and Replacements
                     | 
                    
                        8.6.1.6 General Maintenance Methods
                     | 
                    
                     | 
                    
                     | 
                    
                        Light in hoistway was not working on day of inspection
                     | 
                    
                        
                     | 
                
                
                    | 
                        MO Minimum : Elevators
                     | 
                    
                        2.3 - Lighting and receptacles
                     | 
                    
                        110.27 Guarding of Live Parts NFPA 72
                     | 
                    
                     | 
                    
                     | 
                    
                        A remote stop switch should be installed in overhead where Governor is located
                     | 
                    
                        
                     | 
                
                
                    | 
                        MO Minimum : Elevators
                     | 
                    
                        2.3 - Lighting and receptacles
                     | 
                    
                        110.27 Guarding of Live Parts NFPA 72
                     | 
                    
                     | 
                    
                     | 
                    
                        Provide lighting in governor overhead which is a remote work space, to provide a safe working environment
                     | 
                    
                        
                     | 
                
                
                    | 
                        MO Minimum : Elevators
                     | 
                    
                        2.3 - Lighting and receptacles
                     | 
                    
                        110.27 Guarding of Live Parts NFPA 72
                     | 
                    
                     | 
                    
                     | 
                    
                        Light in hoistway was not working on day of inspection
                     | 
                    
                        
                     | 
                
                
                    | 
                        MO Minimum : Elevators
                     | 
                    
                        (G) - Maintenance, Repair and Replacements
                     | 
                    
                        8.6.1.6 General Maintenance Methods
                     | 
                    
                     | 
                    
                     | 
                    
                        Provide a light in top of hoistway at goverence with 10 switch on wall outside access door
                     | 
                    
                        9/24/2021
                     | 
                
                
                    | 
                        MO Minimum : Elevators
                     | 
                    
                        (G)2-Alterations
                     | 
                    
                        8.7.2.14.2 Car Enclosure
                     | 
                    
                            x
                     | 
                    
                     | 
                    
                        No emergency telephone
                     | 
                    
                        8/21/2020
                     | 
                
                
                    | 
                        MO Minimum : Elevators
                     | 
                    
                        (S) - Fire Service
                     | 
                    
                        (S)1
                     | 
                    
                            x
                     | 
                    
                     | 
                    
                        No audible indication of Phase 1 Fire Service Recall
                     | 
                    
                        8/21/2020
                     | 
                
                
                    | 
                        MO Minimum : Elevators
                     | 
                    
                        CSR 40-5.100 State Operating Certificate
                     | 
                    
                        5.100(2) Display of Operating Certificate
                     | 
                    
                     | 
                    
                     | 
                    
                        Post current state certificate in machine room
                     | 
                    
                        4/1/2021
                     |