Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) Yes No This elevator has a backup emergency generator power that is used in case of a power outage. This system shall be scheduled to be tested and a reinspection is required. This requirement is due to the State of Missouri adopting the A17.1 2016 version of the elevator safety code. 11/8/2023
A17.1-2016 : Elevators 1.17 - Standby power operation 2.27.2 Yes No Emergency power testing failed during inspection and shall be reinspected. 10/23/2025
A17.1-2016 : Elevators 1.6 - Car emergency signal 2.27.1.1.6 Verification of Telephone Operability Yes No Emergency phone line monitoring shall be installed 8/24/2021
A17.1-2016 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Emergency phone line monitoring shall be installed 1/11/2022
A17.1-2016 : Elevators 2.10 - Numbering of Elevators, Machines, Controllers, and Disconnect Switches 2.29.1 Yes No Mark car ID on 110v & main disconnects in electrical room. 8/24/2021
A17.1-2016 : Elevators 2.13 - Governor, Overspeed Switch, and Seal 8.6.4.12 Yes No Governor remote trip in controller is not working, needs repair. Re-inspection required 12/13/2022
A17.1-2016 : Elevators 4.8 - Hoistway enclosure 8.10.3.2.4(h) Yes No Hoistway enclosures shall have flush surfaces on the hoistway side. Enclose or fill in around entrance jambs to meet fire codes at all entrances 8/24/2021