A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.4.19.7 (Re-Inspection)
|
x
|
|
This elevator has a backup emergency generator power that is used in case of a power outage. This system shall be scheduled to be tested and a reinspection is required. This requirement is due to the State of Missouri adopting the A17.1 2016 version of the elevator safety code.
|
11/8/2023
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
2.27.1.1.6 Verification of Telephone Operability
|
x
|
|
Emergency phone line monitoring shall be installed
|
8/24/2021
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone line monitoring shall be installed
|
1/11/2022
|
A17.1-2016 : Elevators
|
2.10 - Numbering of Elevators, Machines, Controllers, and Disconnect Switches
|
2.29.1
|
x
|
|
Mark car ID on 110v & main disconnects in electrical room.
|
8/24/2021
|
A17.1-2016 : Elevators
|
2.13 - Governor, Overspeed Switch, and Seal
|
8.6.4.12
|
x
|
|
Governor remote trip in controller is not working, needs repair. Re-inspection required
|
12/13/2022
|
A17.1-2016 : Elevators
|
4.8 - Hoistway enclosure
|
8.10.3.2.4(h)
|
x
|
|
Hoistway enclosures shall have flush surfaces on the hoistway side. Enclose or fill in around entrance jambs to meet fire codes at all entrances
|
8/24/2021
|