Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing This elevator is equipped with an overspeed valve. Category 5 testing of the valve shall be conducted on or before the next annual inspection.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates Install a code data plate. It shall read: A17.1a - 2005 and A17.1s - 2005.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates A code data tag is required in the machine room.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods The disconnect located in the machine room shall be provided with a sign to identify the location of the supply side overcurrent protective device.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022)
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.2(d) On-Site Documentation (Written Procedures for Evacuation and Cleaning) Written evacuation procedures for elevators by authorized persons and emergency personnel shall be available on-site.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.2(d) On-Site Documentation (Written Procedures for Evacuation and Cleaning) Evacuation procedures are missing from the MCP.
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.2(d)(1) Evacuation procedures for elevators by authorized persons and emergency personnel shall be available on-site.
A17.1-2016 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
A17.1-2016 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
A17.1-2016 : Elevators 2.10 - Numbering of Elevators, Machines, Controllers, and Disconnect Switches 3.29 3.29.1 - The car operating panel identification plate is missing and shall be replaced.
A17.1-2016 : Elevators 1.16 - Rated load, platform area, and data plate 2.16.3 The capacity plate inside the car is missing and shall be replaced. It shall be located in a conspicuous position inside the car.