Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.1(a) Compliant/required documentation & MCP shall be kept in equipment room (neat/organized and not on car top) including wiring diagrams, oil log, and fire service log, recorded monthly. MCP and logs are not being documented properly. 2/14/2024
A17.1-2016 : Elevators 1.6 - Car emergency signal 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Two-way communication device shall give proper location message. Agent said no location message is being given. 3/26/2024
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.1(a) A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. 4/16/2024
A17.1-2016 : Elevators 2.11 - Disconnecting Means and Control 2.26.4.1 x The mechanic turned off the disconnect, then turned it back on, but the controller would not turn back on. Investigate the source of problem and take corrective action. 9/11/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 11/8/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.2(d) On-Site Documentation (Written Procedures for Evacuation and Cleaning) Written evacuation procedures for elevators by authorized persons and emergency personnel shall be available on-site. 11/8/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates Install a code date plate. It shall read A17.1-2016 11/8/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods The disconnect located in the machine room shall be provided with a sign to identify the location of the supply side overcurrent protective device. 11/8/2022
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log A monthly record of findings for firefighters' service operation required by 8.6.11.1 with identification of the person(s) that performed the operation shall be available on-site. 11/8/2022
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x When testing Phase 2 fire service, the mezzanine floor was not over-ridden. 8/26/2022
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO state operating certificate and a state identification sticker shall be posted. 11/8/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x The annual inspection was not finished. The following testing items shall be completed: Relief pressure, emergency light, emergency bell, emergency phone, pressure switch, and low oil timer. 8/26/2022
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x Fire service is not operating properly. The 2nd floor key switch is not overridden when fire service is activated. 10/28/2022