Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records No No A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 11/8/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.2(d) On-Site Documentation (Written Procedures for Evacuation and Cleaning) No No Written evacuation procedures for elevators by authorized persons and emergency personnel shall be available on-site. 11/8/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates No No Install a code date plate. It shall read A17.1-2016 11/8/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods No No The disconnect located in the machine room shall be provided with a sign to identify the location of the supply side overcurrent protective device. 11/8/2022
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log No No A monthly record of findings for firefighters' service operation required by 8.6.11.1 with identification of the person(s) that performed the operation shall be available on-site. 11/8/2022
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current MO state operating certificate and a state identification sticker shall be posted. 11/8/2022
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.1(a) No No Compliant/required documentation & MCP shall be kept in equipment room (neat/organized and not on car top) including wiring diagrams, oil log, and fire service log, recorded monthly. MCP and logs are not being documented properly. 2/14/2024
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.1(a) No No A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. 4/16/2024
A17.1-2016 : Elevators 2.4 - Machine space 8.6.4.8 Machine Room and Machinery Space No No Top floor is a machien space that requires 19 foot candles of lighting in fron of door jam. 12/19/2025
A17.1-2016 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Up to date operating certificate required in the elevator machine room. 12/19/2025
A17.1-2016 : Elevators 2.11 - Disconnecting Means and Control 2.26.4.1 Yes No The mechanic turned off the disconnect, then turned it back on, but the controller would not turn back on. Investigate the source of problem and take corrective action. 9/11/2024
A17.1-2016 : Elevators 1.6 - Car emergency signal 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Two-way communication device shall give proper location message. Agent said no location message is being given. 3/26/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No The annual inspection was not finished. The following testing items shall be completed: Relief pressure, emergency light, emergency bell, emergency phone, pressure switch, and low oil timer. 8/26/2022
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) Yes No Fire service is not operating properly. The 2nd floor key switch is not overridden when fire service is activated. 10/28/2022
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) Yes No When testing Phase 2 fire service, the mezzanine floor was not over-ridden. 8/26/2022