Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 1.6 - Car emergency signal 2.27.1.1.1 Emergency communications and alarm not functioning (Red Tag) x 2 way communication not active at this time 12/18/2020
A17.1-2016 : Elevators 1.6 - Car emergency signal 2.27.1.1.6 Verification of Telephone Operability verification not working 1/3/2022
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x emg. Lt. an bell not working 1/3/2022
A17.1-2016 : Elevators 2.4 - Machine space 8.6.1.6.5 Fire Extinguishers x Supply ABC fire extinguisher in Machine Room 12/18/2020
A17.1-2016 : Elevators 2.4 - Machine space 2.7.3 x Provide closer for Machine Room Door 12/18/2020
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.5 x Provide light and GFCI in pit area 12/18/2020
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 3.27.3 Device Actuation at Recall Level x x No Smoke detectors in the elevator lobbies 12/18/2020