Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 3.13 - Windows, projections, recesses, and setbacks 2.1.6 x Beams in the back of the hoistway and concrete ledge in the pit shall be beveled to an angle not less than 75 degrees. 6/30/2021
A17.1-2016 : Elevators 11.10 - Governor, Overspeed Switch 2.18.7.2 Govenor tail sheave switch is not working 4/5/2022
A17.1-2016 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Phone not working correctly, repair as needed. 6/8/2022
A17.1-2016 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency phone is not working. Re-inspection required 4/19/2022
A17.1-2016 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Video monitoring is not working and shall be operational. (Phone is working) 2/29/2024
A17.1-2016 : Elevators 1.6 - Car emergency signal 2.27.1.1.6 Verification of Telephone Operability Phone line monitor is not working correctly 6/7/2022
A17.1-2016 : Elevators 1.6 - Car emergency signal 2.27.1.1.6 Verification of Telephone Operability Phone line monitoring not working correctly, repair as needed. Reinspect required. 4/5/2022
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3 x x Phase 1 & 2 fire service and all initiating devices shall be tested. 6/30/2021
A17.1-2016 : Elevators 2.1 - Access to machine space 2.7.3.4 x The machine room door shall be self-closing and self-locking. 6/30/2021
A17.1-2016 : Elevators 4.8 - Hoistway enclosure 8.10.2.2.4(h) x Screws protruding into the hoistway shall be removed. 6/30/2021
A17.1-2016 : Elevators 4.8 - Hoistway enclosure 8.10.2.2.4(h) x The door at the top of the hoistway shall be blocked up. 6/30/2021
A17.1-2016 : Elevators 2.42 - Earthquake Inspection and Tests (Seismic Risk Zone 2 or Greater) 8.4 Counterweight derailment device is not working 4/5/2022
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Video monitoring does not work.
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits The pit shall be kept clean. Clean the pit.