A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency communications loss monitor shall work.
|
8/24/2023
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.2.2 On-Site Documentation
|
|
|
Fire service checklist shall be provided in the MCP.
|
9/22/2022
|
A17.1-2016 : Elevators
|
4.2 - Hoistway doors
|
2.11
|
x
|
|
The top and bottom of horizontally sliding doors shall be provided with a means of retaining the closed door panel in position if the primary guiding means fail. The hoistway door safety retainers are missing from the bottom of the door panels and shall be installed.
|
8/31/2022
|
A17.1-2016 : Elevators
|
9.19 - Maintenance Records
|
8.6.1.2.1(a)
|
|
|
A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. No maintenance/repair records.
|
9/22/2022
|
A17.1-2016 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Post current State Operating Certificate in machine room.
|
9/22/2022
|