Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3 Yes Yes move smoke detector at least 3 ft from air vent 7/19/2021
A17.1-2016 : Elevators 2.1 - Access to machine space 2.7.3.4 Yes No Machine Room door shall be self Closing and self locking 7/19/2021
A17.1-2016 : Elevators 2.3 - Lighting and receptacles 2.7.9.1 Yes No Light switch is automatic motion. Needs to be Manual 7/19/2021
A17.1-2016 : Elevators 2.8 - Pipes, wiring, and ducts 2.8 Yes No install heat detector 2ft or less from sprinkler head in machine room 7/19/2021
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.4.19.6 Yes No Test all smoke and heat devices 7/19/2021
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) Yes No Provide existing battery backup lowering unit to work. 11/25/2025
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) Yes No Repair inoperative auxillary battery lowering 3/24/2026
A17.1-2016 : Elevators 5.15 - Overspeed Valve 8.6.5.16.5 Yes No OSV is due for testing, provide.