MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
x
|
|
Provide ABC Fire Extinguisher in Machine Space 8.6.1.6.5
|
7/13/2022
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)1
|
|
|
Means of access to machine space door shall be clear and unobstructed. Metal stands blocking door opening.
|
10/23/2024
|
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
8.10.2.2.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency Phone in car fails to establish two-way communication. No dial tone. 3.27
|
7/13/2022
|
|
A17.1-2016 : Elevators
|
2.1 - Access to machine space
|
8.10.3.2.2(d)
|
x
|
|
Machine Room door needs to open farther to allow proper clearance access to the controller 3.7
|
7/13/2022
|
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.2.1(a)
|
|
|
A code compliant MCP and all the on-site documentation required shall be provided in the machine room.
|
10/23/2024
|
|
A17.1-2016 : Elevators
|
2.7 - Fire Extinguisher
|
8.6.1.6.5
|
|
|
Machine room shall have proper fire extinguisher and shall have current monthly/annual test tag.
|
10/23/2024
|
|
A17.1-2016 : Elevators
|
3.10 - Hoistway construction
|
8.7.2.1.1(b)
|
x
|
|
Hoistway needs to be fully enclosed with a two hour Fire rating. Remove wood decking at third floor landing behind fascia. 3.1
|
7/13/2022
|