A17.1-2016 : Elevators
|
3.13 - Windows, projections, recesses, and setbacks
|
2.1.6
|
x
|
|
Remove all protruding sheetrock screws from hoistway walls.
|
2/21/2022
|
A17.1-2016 : Elevators
|
2.10 - Numbering of Elevators, Machines, Controllers, and Disconnect Switches
|
8.10.2.2.2(o)
|
x
|
|
Provide feed source location for elevator main line disconnect, and label on disconnect at the 2nd floor access panel.
|
2/21/2022
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.3.2 Phase I Operation Recall by Initiating Device
|
x
|
x
|
FFS installation incomplete, unable to test.
|
2/21/2022
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.10.2.2.1(q)
|
x
|
|
The generator for the facility has not yet been installed, standby power is not ready to test.
|
2/21/2022
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
2.27.1.1.6 Verification of Telephone Operability
|
x
|
|
No phone service to building at this time, unable to test emergency phone.
|
2/21/2022
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.2.2 On-Site Documentation
|
|
|
No written documentation on-site.
|
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.4 Instructions for Locating Maintenance Records
|
|
|
No instructions posted for locating maintenance records.
|
|