Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 3.13 - Windows, projections, recesses, and setbacks 2.1.6 x Remove all protruding sheetrock screws from hoistway walls. 2/21/2022
A17.1-2016 : Elevators 1.6 - Car emergency signal 2.27.1.1.6 Verification of Telephone Operability x No phone service to building at this time, unable to test emergency phone. 2/21/2022
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.2 Phase I Operation Recall by Initiating Device x x FFS installation incomplete, unable to test. 2/21/2022
A17.1-2016 : Elevators 1.17 - Standby power operation 8.10.2.2.1(q) x The generator for the facility has not yet been installed, standby power is not ready to test. 2/21/2022
A17.1-2016 : Elevators 2.10 - Numbering of Elevators, Machines, Controllers, and Disconnect Switches 8.10.2.2.2(o) x Provide feed source location for elevator main line disconnect, and label on disconnect at the 2nd floor access panel. 2/21/2022
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.2 On-Site Documentation No written documentation on-site.