Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 2.27.2 Yes No Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. 12/28/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 2.27.2 Yes No The emergency/standby power shall be tested. 11/16/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Incomplete test. At this time emergency power testing and Overspeed valve testing is still due.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 No No An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door. 12/8/2023