A17.1-2016 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
2.8.3
|
x
|
|
the shunt trip breaker was not ready to test
|
1/25/2021
|
A17.1-2016 : Elevators
|
2.3 - Lighting and receptacles
|
3.7.1
|
x
|
|
need more light over the controller access door, measured 7 foot candles at the floor, the requirement is minimum of 19 foot candles
|
1/25/2021
|
A17.1-2016 : Elevators
|
2.1 - Access to machine space
|
3.7.1
|
x
|
|
the automatic door closer for the controller access door has not been installed
|
1/25/2021
|
A17.1-2016 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
2.8
|
x
|
|
feeder locations need to be marked on the mainline disconnect and 110 volt disconnect.
|
1/25/2021
|
A17.1-2016 : Elevators
|
1.13 - Emergency exit
|
8.11.3.1.1(m)
|
|
|
the escape hatch is bolted closed, need to change the bolts for wing nuts so can be opened with out tools
|
3/3/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.2.2(a) On-Site Documentation (Up-to-Date Wiring Diagrams)
|
|
|
the wiring diagrams are not in the machine room
|
3/3/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4.1(a) On-Site Maintenance Records (MCP Records)
|
|
|
Maintenance Control Program (MCP) is not in the machine room
|
3/3/2022
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.6.11.1 Monthly Test and Log
|
|
|
the monthly fire service test log is not in the machine room
|
3/3/2022
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
a copy of the state operating certificate is to be posted in the machine room
|
3/3/2022
|