Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate a copy of the state operating certificate is to be posted in the machine room 3/3/2022
A17.1-2016 : Elevators 2.8 - Pipes, wiring, and ducts 2.8 x feeder locations need to be marked on the mainline disconnect and 110 volt disconnect. 1/25/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) Maintenance Control Program (MCP) is not in the machine room 3/3/2022
A17.1-2016 : Elevators 2.3 - Lighting and receptacles 3.7.1 x need more light over the controller access door, measured 7 foot candles at the floor, the requirement is minimum of 19 foot candles 1/25/2021
A17.1-2016 : Elevators 2.1 - Access to machine space 3.7.1 x the automatic door closer for the controller access door has not been installed 1/25/2021
A17.1-2016 : Elevators 1.13 - Emergency exit 8.11.3.1.1(m) the escape hatch is bolted closed, need to change the bolts for wing nuts so can be opened with out tools 3/3/2022
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log the monthly fire service test log is not in the machine room 3/3/2022
A17.1-2016 : Elevators 2.8 - Pipes, wiring, and ducts 2.8.3 x the shunt trip breaker was not ready to test 1/25/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.2(a) On-Site Documentation (Up-to-Date Wiring Diagrams) the wiring diagrams are not in the machine room 3/3/2022