Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 1.6 - Car emergency signal 2.27.1.1.6 Verification of Telephone Operability x Message states Elevator “A”, caller ID labeled “B”. Caller ID needs to be for “A” 12/15/2021
A17.1-2016 : Elevators 1.6 - Car emergency signal 2.27.1.1.6 Verification of Telephone Operability Message states Elevator “A”, caller ID labeled “B”. Caller ID needs to be for “A” 12/15/2021
A17.1-2016 : Elevators 3.10 - Hoistway construction 3.1 TOP OF HOISTWAY: Touch-up fire caulking on non-factory horizontal joints and cracks and Northeast vertical corner 12/15/2021
A17.1-2016 : Elevators 3.10 - Hoistway construction 3.1 x TOP OF HOISTWAY: Touch-up fire caulking on non-factory horizontal joints and cracks and Northeast vertical corner 12/15/2021
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2.5 Sump Pump Required/Capacity (Re-Inspect) x Pit Sump Pump is required(installed) , electrical outlet missing. Install outlet, connect pump, test pump operation. 12/15/2021
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2.5 Sump Pump Required/Capacity (Re-Inspect) x Pit Sump Pump is required(installed) , electrical outlet missing. Install outlet, connect pump, test pump operation. 12/15/2021
A17.1-2016 : Elevators 6.5 -Acceptance Checklist for Firefighters' Service (ASME A17.1-2000 and CSA B44-00): Automatic Elevators 3.27.1 x 17.1-2016: 2.27.9 : Replace missing hall fire signage “ in case of fire…..” 12/15/2021
A17.1-2016 : Elevators 6.5 -Acceptance Checklist for Firefighters' Service (ASME A17.1-2000 and CSA B44-00): Automatic Elevators 3.27.1 x 17.1-2016: 2.27.9 : Replace missing hall fire signage “ in case of fire…..” 12/15/2021