Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 1.17 - Standby power operation 8.10.2.2.1(q) Yes No Test emergency power operation 10/1/2021
A17.1-2016 : Elevators 2.18 - Traction drive machines 8.10.2.2.2(w) Yes No Provide means for, and test, traction loss 10/1/2021
A17.1-2016 : Elevators 1.6 - Car emergency signal 2.27.1.1.6 Verification of Telephone Operability Yes No Provide monitoring of telephone operability 10/1/2021
A17.1-2016 : Elevators 3.13 - Windows, projections, recesses, and setbacks 2.1.6 Yes No Install vented covers on air pressurization ducts to eliminate recess in hoistway wall 10/1/2021
A17.1-2016 : Elevators 2.7 - Fire Extinguisher 8.10.2.2.2(l) Yes No Provide type ABC fire extinguisher inside control space 10/1/2021
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.4.1(d) Yes No Provide acceptance test tag with applicable code requirements with the dates tests are performed, firm performing test, inspector witnessing tests, inspector name and certifying organization. Permanently attach to controller. 10/1/2021
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) Yes No Test operation of elevator on emergency power 11/9/2022
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) Yes No Test emergency power operation 12/13/2023
A17.1-2016 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No State operating certificate not displayed 1/5/2024
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.1(a) No No No MCP 2/1/2024
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) Yes No The emergency power was not tested. 11/13/2024