Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 1.17 - Standby power operation 8.10.2.2.1(q) x Test emergency power operation 10/1/2021
A17.1-2016 : Elevators 2.18 - Traction drive machines 8.10.2.2.2(w) x Provide means for, and test, traction loss 10/1/2021
A17.1-2016 : Elevators 1.6 - Car emergency signal 2.27.1.1.6 Verification of Telephone Operability x Provide monitoring of telephone operability 10/1/2021
A17.1-2016 : Elevators 3.13 - Windows, projections, recesses, and setbacks 2.1.6 x Install vented covers on air pressurization ducts to eliminate recess in hoistway wall 10/1/2021
A17.1-2016 : Elevators 2.7 - Fire Extinguisher 8.10.2.2.2(l) x Provide type ABC fire extinguisher inside control space 10/1/2021
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.4.1(d) x Provide acceptance test tag with applicable code requirements with the dates tests are performed, firm performing test, inspector witnessing tests, inspector name and certifying organization. Permanently attach to controller. 10/1/2021
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.1(a) No MCP 2/1/2024
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x Test operation of elevator on emergency power 11/9/2022
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x Test emergency power operation 12/13/2023
A17.1-2016 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate State operating certificate not displayed 1/5/2024
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x The emergency power was not tested. 11/13/2024