Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A18.1-2005 : Lifts & Chairlifts 2.1 - Runways 2.1.1.4 Provide electric/mechanical interlock for upper landing gate. 9/30/2024
ASME A18.1-2005 : Lifts & Chairlifts 2.1 - Runways 2.1.1.4 Provide electrical/mechanical interlock for lower landing door. 9/30/2024
ASME A18.1-2005 : Lifts & Chairlifts 2.1 - Runways 2.1.1.6 Running clearance between sill @ rear entrance under .375 inch minimum. 9/30/2024
ASME A18.1-2005 : Lifts & Chairlifts 2.1 - Runways 2.1.1.7 Clearance between platform guardrail and wall is 5 1/2". The tolerance is no less than 2", no more than 3". 9/30/2024
ASME A18.1-2005 : Lifts & Chairlifts 2.1 - Runways 2.1.1.1 Provide solid enclosure of hoistway for entirety of hoistway. 9/30/2024
ASME A18.1-2005 : Lifts & Chairlifts 2.1 - Runways 2.1.7 Provide fused, lockable main line disconnect for lift power within sight of lift. 9/30/2024
ASME A18.1-2005 : Lifts & Chairlifts 2.1 - Runways 2.1.2.2 Top landing gate and surrounding walls shall be a minimum of 42" tall from landing floor. 9/30/2024
ASME A18.1-2005 : Lifts & Chairlifts 2.10 - Operating Devices and Control Equipment 2.10.1 x Provide call/send stations at each landing @ maximum height of 48" from the landing floor. 10/18/2021
ASME A18.1-2005 : Lifts & Chairlifts 2.11 - Emergency Signals 2.11.1 x Provide audible alarm upon activation of emergency stop switch. 10/18/2021
ASME A18.1-2005 : Lifts & Chairlifts 2.6 - Platforms 2.6.6.3 Auxiliary Lighting (Re-Inspection) Provide emergency overhead lighting in hoistway. 7/18/2024
ASME A18.1-2005 : Lifts & Chairlifts 2.6 - Platforms 2.6.3 Enclosure walls shall not deform more than one inch. 9/30/2024
ASME A18.1-2005 : Lifts & Chairlifts 2.7 - Capacity, Speed, and Travel 2.7.2 Provide capacity plates with operating instructions at each landing. 9/30/2024
ICC A117.1-2009 410.2 - Lift Entry 410.2.1 Provide low energy power operators at each landing door/gate. 9/30/2024
ASME A18.1-2005 : Lifts & Chairlifts CSR 40-5.100 State Operating Certificate 5.100(2) display of certificate State Operating Certificate not available. Present site contact person has changed, however the Email address is correct.
ASME A18.1-2005 : Lifts & Chairlifts CSR 40-5.100 State Operating Certificate 5.100(2) display of certificate Initial Violations have been corrected. Operating Certificate not available!