ASME A18.1-2005 : Lifts & Chairlifts
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) display of certificate
|
|
|
State Operating Certificate not available. Present site contact person has changed, however the Email address is correct.
|
|
ASME A18.1-2005 : Lifts & Chairlifts
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) display of certificate
|
|
|
Initial Violations have been corrected. Operating Certificate not available!
|
|
ASME A18.1-2005 : Lifts & Chairlifts
|
2.11 - Emergency Signals
|
2.11.1
|
x
|
|
Provide audible alarm upon activation of emergency stop switch.
|
10/18/2021
|
ASME A18.1-2005 : Lifts & Chairlifts
|
2.10 - Operating Devices and Control Equipment
|
2.10.1
|
x
|
|
Provide call/send stations at each landing @ maximum height of 48" from the landing floor.
|
10/18/2021
|
ASME A18.1-2005 : Lifts & Chairlifts
|
2.6 - Platforms
|
2.6.6.3 Auxiliary Lighting (Re-Inspection)
|
|
|
Provide emergency overhead lighting in hoistway.
|
7/18/2024
|
ASME A18.1-2005 : Lifts & Chairlifts
|
2.7 - Capacity, Speed, and Travel
|
2.7.2
|
|
|
Provide capacity plates with operating instructions at each landing.
|
9/30/2024
|
ASME A18.1-2005 : Lifts & Chairlifts
|
2.1 - Runways
|
2.1.7
|
|
|
Provide fused, lockable main line disconnect for lift power within sight of lift.
|
9/30/2024
|
ASME A18.1-2005 : Lifts & Chairlifts
|
2.1 - Runways
|
2.1.2.2
|
|
|
Top landing gate and surrounding walls shall be a minimum of 42" tall from landing floor.
|
9/30/2024
|
ICC A117.1-2009
|
410.2 - Lift Entry
|
410.2.1
|
|
|
Provide low energy power operators at each landing door/gate.
|
9/30/2024
|
ASME A18.1-2005 : Lifts & Chairlifts
|
2.1 - Runways
|
2.1.1.4
|
|
|
Provide electric/mechanical interlock for upper landing gate.
|
9/30/2024
|
ASME A18.1-2005 : Lifts & Chairlifts
|
2.1 - Runways
|
2.1.1.4
|
|
|
Provide electrical/mechanical interlock for lower landing door.
|
9/30/2024
|
ASME A18.1-2005 : Lifts & Chairlifts
|
2.1 - Runways
|
2.1.1.6
|
|
|
Running clearance between sill @ rear entrance under .375 inch minimum.
|
9/30/2024
|
ASME A18.1-2005 : Lifts & Chairlifts
|
2.1 - Runways
|
2.1.1.7
|
|
|
Clearance between platform guardrail and wall is 5 1/2". The tolerance is no less than 2", no more than 3".
|
9/30/2024
|
ASME A18.1-2005 : Lifts & Chairlifts
|
2.1 - Runways
|
2.1.1.1
|
|
|
Provide solid enclosure of hoistway for entirety of hoistway.
|
9/30/2024
|
ASME A18.1-2005 : Lifts & Chairlifts
|
2.6 - Platforms
|
2.6.3
|
|
|
Enclosure walls shall not deform more than one inch.
|
9/30/2024
|