Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 1/19/2024
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits The pit shall be kept clean. Clean the pit. 1/19/2024
A17.1-2016 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The emergency phone is working, but video monitoring is not operational at this time. Take corrective action and re-inspect ASAP. 1/19/2024
A17.1-2016 : Elevators 4.2 - Hoistway doors 2.11 x The top and bottom oh horizontally sliding doors shall be provided with a means of retaining the closed door panel in position if the primary guiding means fail. The hoistway door safety retainers are missing from the bottom of the door panel and shall be installed. 7/3/2023
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x The emergency power indicator light at the egress floor must be operational. 7/3/2023
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The in car emergency telephone shall be operational. 7/3/2023
A17.1-2016 : Elevators 4.2 - Hoistway doors 2.11 x The top and bottom oh horizontally sliding doors shall be provided with a means of retaining the closed door panel in position if the primary guiding means fail. The hoistway door safety retainers are missing from the bottom of the door panel and shall be installed. (2nd Notice) 1/19/2024
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. The emergency power indicator light shall be operational on the egress floor. 1/19/2024
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.4 Instructions for Locating Maintenance Records x A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 8/3/2021
A17.1-2016 : Elevators 5.2 - Bottom clearance, runby, and minimum refuge space 8.10.2.2.5(b) x A counterweight guard shall be installed. 8/3/2021
A17.1-2016 : Elevators 5.2 - Bottom clearance, runby, and minimum refuge space 8.10.2.2.5(b) x Counterweight runby signage shall be installed. 8/3/2021
A17.1-2016 : Elevators 1.17 - Standby power operation 8.10.2.2.1(q) x Emergency/standby power operation of the elevator shall be tested. 8/3/2021
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.10.2.2.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The in car emergency telephone shall be operational. 8/3/2021
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.7 Firefighters’ Emergency Operation: Operating Procedures (Signage) x Fire service signage shall be installed. 8/3/2021
A17.1-2016 : Elevators 1.4 - Sills and car floor 8.10.2.2.1(d) x Permanent flooring shall be installed in the elevator cab. 8/3/2021
A17.1-2016 : Elevators 1.17 - Standby power operation 8.10.2.2.1(q) x Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. 10/21/2021