Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 1.6 - Car emergency signal 2.27.1.1.6 Verification of Telephone Operability x Provide a working phone line. 9/30/2021
A17.1-2016 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Provide a working emergency phone yours still don't work. 9/30/2021
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.1(a) x Provide a written Maintenance Control Program in the machine space. 9/30/2021
A17.1-2016 : Elevators 3.10 - Hoistway construction 2.1 x Fire caulk all open penatrations into the hoistway 9/30/2021
A17.1-2016 : Elevators 3.12 - Pipes, wiring, and ducts 2.8 x Encase the added ventilation wiring in conduit at the top of the hoistway. 9/30/2021
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.4 x Add rungs all the way up to the top of the handrails to provide hand holds, since the ladder is to close to the rail. 9/30/2021
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2.5 Sump Pump Required/Capacity (Re-Inspect) x Provide documentation as to the capability of the installed sump pump. Will it discharge 3000gph sufficiently and where does it discharge to? 9/30/2021
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.4 x Add rungs all the way up to the top of the pit ladder to be used for hamdrails as the side rails are to close to obstructions to be of any use. 9/30/2021
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.2 Phase I Operation Recall by Initiating Device x x Move the smoke detector at the top of the hoistway up to within 12" of the ceiling and have all the system tested 9/30/2021