Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) Yes No All smokes, machine room heat, shunt trip, and pit sprinkler flow switch shall be tested. 12/16/2021
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard Yes No The building corridors shall be so lighted that the illumination at the landing sills, when an elevator is in service, shall be not less than 10 foot-candles. 12/16/2021
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.10.2.2.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No The in car emergency telephone shall be operational. 12/16/2021
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 3.27.3 Device Actuation at Recall Level Yes Yes When sprinklers are installed in elevator pits, automatic fire detection shall be installed to initiate elevator recall in accordance with 3.27. A waterflow switch shall be permitted to initiate elevator recall upon activation of a sprinkler installed in the elevator pit, provided the waterflow switch and pit sprinkler are installed on a separately valved sprinkler line dedicated solely for protecting the elevator pit, and the waterflow switch is provided without time-delay capability. Note: the flow switch shall activate the fire hat and alternate floor recall. 12/16/2021
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.9 Elevator Corridor Call Station Pictograph Yes No A sign shall be posted adjacent to hall call fixtures instructing occupants not to use the elevator in case of a fire, the sign shown in A17.1 2016, figure 2.27.9 shall be provided. The sign shall include only the wording and graphics shown in figure 2.27.9. 12/16/2021
A17.1-2016 : Elevators 2.3 - Lighting and receptacles 8.10.3.2.2(h) Yes No At least one duplex GFCI receptacle shall be provided in the machine room. 12/16/2021
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.10.3.2.5(a) Yes No Illumination of the pit shall not be less than 10 foot-candles measured at the pit floor. 12/16/2021
A17.1-2016 : Elevators 3.13 - Windows, projections, recesses, and setbacks 3.1 Yes No Exposed fasteners protruding into the hoistway from the ceiling and walls shall be removed. 12/16/2021
A17.1-2016 : Elevators 3.13 - Windows, projections, recesses, and setbacks 2.1.6 Yes No Where recesses or setbacks exceeding 4 inches occur in the enclosure wall, the top of the recess or setbacks shall be beveled at and angle of not less than 75 degrees with the horizontal. 12/16/2021
A17.1-2016 : Elevators 2.1 - Access to machine space 2.7.1.1 No No Label the machine room door in case of emergency. 2/16/2023
A17.1-2016 : Elevators 1.6 - Car emergency signal 2.11.1.3 Emergency Phone not workng Alarm Functioning ( Mandatory Re-Inspection due in 14 days) Yes No The phone shall establish 2-way communication. 12/4/2025