Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x The building corridors shall be so lighted that the illumination at the landing sills, when an elevator is in service, shall be not less than 10 foot-candles. 12/16/2021
A17.1-2016 : Elevators 3.13 - Windows, projections, recesses, and setbacks 2.1.6 x Where recesses or setbacks exceeding 4 inches occur in the enclosure wall, the top of the recess or setbacks shall be beveled at and angle of not less than 75 degrees with the horizontal. 12/16/2021
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.9 Elevator Corridor Call Station Pictograph x A sign shall be posted adjacent to hall call fixtures instructing occupants not to use the elevator in case of a fire, the sign shown in A17.1 2016, figure 2.27.9 shall be provided. The sign shall include only the wording and graphics shown in figure 2.27.9. 12/16/2021
A17.1-2016 : Elevators 2.1 - Access to machine space 2.7.1.1 Label the machine room door in case of emergency. 2/16/2023
A17.1-2016 : Elevators 3.13 - Windows, projections, recesses, and setbacks 3.1 x Exposed fasteners protruding into the hoistway from the ceiling and walls shall be removed. 12/16/2021
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 3.27.3 Device Actuation at Recall Level x x When sprinklers are installed in elevator pits, automatic fire detection shall be installed to initiate elevator recall in accordance with 3.27. A waterflow switch shall be permitted to initiate elevator recall upon activation of a sprinkler installed in the elevator pit, provided the waterflow switch and pit sprinkler are installed on a separately valved sprinkler line dedicated solely for protecting the elevator pit, and the waterflow switch is provided without time-delay capability. Note: the flow switch shall activate the fire hat and alternate floor recall. 12/16/2021
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.10.2.2.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The in car emergency telephone shall be operational. 12/16/2021
A17.1-2016 : Elevators 2.3 - Lighting and receptacles 8.10.3.2.2(h) x At least one duplex GFCI receptacle shall be provided in the machine room. 12/16/2021
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.10.3.2.5(a) x Illumination of the pit shall not be less than 10 foot-candles measured at the pit floor. 12/16/2021
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x All smokes, machine room heat, shunt trip, and pit sprinkler flow switch shall be tested. 12/16/2021