A17.1-2016 : Elevators
|
3.4 - Top-of-car Clearance, Refuge Space, & Standard Railing
|
2.10.2.3 Toe Board
|
x
|
|
Cartop railing clearance only 3" from hoistway.
|
5/18/2021
|
A17.1-2016 : Elevators
|
3.27 - Crosshead Data Plate and Rope Data Tags
|
8.10.2.2.3(k)
|
x
|
|
Complete labeling of cartop data plate with permanent means.
|
5/18/2021
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Fire service was not ready to be tested, installation of initiating devices is incomplete.
|
5/18/2021
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
no current cirt on site
|
|
A17.1-2016 : Elevators
|
2.7 - Fire Extinguisher
|
8.10.2.2.2(l)
|
x
|
|
Provide fire extinguisher within sight of machine space at top landing.
|
5/18/2021
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
8.10.2.2.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Provide means of two way communication for elevator car monitored 24 hrs a day.
|
5/18/2021
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.4
|
x
|
|
Provide pit ladder.
|