Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 1.6 - Car emergency signal 2.27.1.1.1 Emergency communications and alarm not functioning (Red Tag) x x 2-way communication device shall work, no alarm button installed. Red tag issued. 2/12/2026
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x 2-WAY COMMUNICATION DEVICE SHALL WORK with loss of 120v. Phone is working, Backup battery charger is faulty.
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.2 On-Site Documentation Compliant/required documentation shall be kept in the equipment room (neat/orginized) including MCP, wiring diagrams, PM log, callback log, oil log, fire service log (tested monthly, and evacuation procedures. No documentation present for 2021, 2022, 2023, 2024, & 2025 2/12/2026