A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.2.2 On-Site Documentation
|
No
|
No
|
Compliant/required documentation shall be kept in the equipment room (neat/orginized) including MCP, wiring diagrams, PM log, callback log, oil log, fire service log (tested monthly, and evacuation procedures. No documentation present for 2021, 2022, 2023, 2024, & 2025
|
2/12/2026
|
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
2.27.1.1.1 Emergency communications and alarm not functioning (Red Tag)
|
Yes
|
Yes
|
2-way communication device shall work, no alarm button installed. Red tag issued.
|
2/12/2026
|
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
Yes
|
No
|
2-WAY COMMUNICATION DEVICE SHALL WORK with loss of 120v. Phone is working, Backup battery charger is faulty.
|
3/17/2026
|
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
Yes
|
No
|
2-WAY COMMUNICATION DEVICE SHALL WORK with loss of 120v. Phone is working, Backup battery charger is faulty.
|