Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3 x x Fire caulk around the top of the hoistway and hall door 2nd. level. 8/5/2021
A17.1-2016 : Elevators 3.11 - Hoistway smoke control 8.10.2.2.3(q) x Install a heat detector and smoke detector at the top of the hoistway within 2 feet of the sprinkler head. 8/5/2021
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.4 x x Install a smoke detector in the controller cabinet. and test all fire system. 8/5/2021
A17.1-2016 : Elevators 1.5 - Car lighting and receptacles 8.10.2.2.1(e) x Provide 110 volt electricity to the car lighting , inside the car and on top of the car. 8/5/2021
A17.1-2016 : Elevators 1.6 - Car emergency signal 2.27.1.1.1 Emergency communications and alarm not functioning (Red Tag) x Provide a working emergency phone . The incoming line is dead, no dial tone. 8/5/2021