A17.1-2016 : Elevators
|
3.10 - Hoistway construction
|
2.1
|
x
|
|
2nd and 3rd flr header area needs to be filled and sealed
|
7/22/2022
|
A17.1-2016 : Elevators
|
4.8 - Hoistway enclosure
|
2.1.1
|
x
|
|
All floor entrance frames need to finish completely sealing around.
|
7/22/2022
|
A17.1-2016 : Elevators
|
2.4 - Machine space
|
2.8.1
|
x
|
|
Heat sensor over 24 inches from sprinkler head in control space. As per NFPA 70 21.4.2*
|
7/22/2022
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
emg phone not working wont dial out
|
1/15/2024
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.2.2 On-Site Documentation
|
|
|
no mcp on site
|
1/17/2024
|
A17.1-2016 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
no current cirt displayed
|
1/17/2024
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
emg phone not working
|
1/17/2024
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
x
|
|
Clean hoistway construction debris from pit
|
7/22/2022
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)8
|
x
|
|
Sump pump hole needs cover
|
7/22/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
x
|
|
Fire extinguisher needed for control space. (Controller on jam)
|
7/22/2022
|