Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.2 On-Site Documentation No No no mcp on site 1/17/2024
A17.1-2016 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No no current cirt displayed 1/17/2024
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No emg phone not working 1/17/2024
A17.1-2016 : Elevators 2.4 - Machine space 2.8.1 Yes No Heat sensor over 24 inches from sprinkler head in control space. As per NFPA 70 21.4.2* 7/22/2022
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No emg phone not working wont dial out 1/15/2024
A17.1-2016 : Elevators 3.10 - Hoistway construction 2.1 Yes No 2nd and 3rd flr header area needs to be filled and sealed 7/22/2022
A17.1-2016 : Elevators 4.8 - Hoistway enclosure 2.1.1 Yes No All floor entrance frames need to finish completely sealing around. 7/22/2022
MO Minimum : Elevators (I) - Pits (I)1 Yes No Clean hoistway construction debris from pit 7/22/2022
MO Minimum : Elevators (I) - Pits (I)8 Yes No Sump pump hole needs cover 7/22/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers Yes No Fire extinguisher needed for control space. (Controller on jam) 7/22/2022