Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 2.27 - Rope fastenings 8.11.2.1.2(cc) The car and counterweight retaining clips shall be spaced correctly. The first clip shall be placed a maximum of 4 times the rope diameter above the socket, and the second clip shall be located within 8 times the rope diameter above the first clip.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates A governor rope data tag shall be provided.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers The fire extinguisher in the machine room is expired.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. A maintenance check chart and wiring diagrams are the only items present.
MO Minimum : Elevators (H) - Machine Rooms (H)8 Label the disconnect with the location, source, and breaker numbers of the panel from which it is fed.
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be obtained and displayed in the elevator machine room.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022)
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x The in car emergency lighting shall be operational. 6/8/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x The in car emergency bell shall be operational with 110v source removed. 6/8/2021
MO Minimum : Elevators (S) - Fire Service 211.7 Firefighters Operations/Signage Provide fire service Phase 2 instructions inside the car.
MO Minimum : Elevators (I) - Pits (I)1 The pit shall be kept clean and dry. Clean the pit.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.9 Cleaning of Top of Cars The car top shall be cleaned.
MO Minimum : Elevators (A) - Hoistways (A)16 Install missing electrical box covers on the car top.
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be obtained and displayed in the elevator machine room.
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)1(A) The hoist ropes shall have data tags installed.
MO Minimum : Elevators (A) - Hoistways (A)16 All electrical wires in the hoistway shall be enclosed in conduit or metal raceway, or be in compliance with NFPA 70.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x The in car emergency telephone shall be operational. 6/8/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods The car operating panel shall be secured.
MO Minimum : Elevators (A) - Hoistways (A)13 Hoistways shall be fully enclosed and made of solid construction.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates Unit shall have a code compliant code data plate.
MO Minimum : Elevators (H) - Machine Rooms (H)8 Install missing duct covers and electrical box covers in the machine room.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods The pit door shall be self-closing and self-locking. It is also recommended that a warning/danger sign be put on the pit door.
MO Minimum : Elevators (S) - Fire Service (S)1 x x Phase 2 fire service switch shall be two position type. Shall not have bypass feature operational. Unit Red Tagged. 6/8/2021
MO Minimum : Elevators (S) - Fire Service (S)1 x x Fire alarm initiating devices (smoke detectors) shall be provided and shall active Phase 1 fire service. Unit Red Tagged. 6/8/2021
MO Minimum : Elevators (S) - Fire Service (S)1 x x The fire service Phase 2 key switch shall be operational. Unit Red Tagged. 6/8/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods All car top electrical boxes shall have covers installed.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates "In Case of Fire" signage shall be installed at each landing.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x The in car emergency lighting shall be operational. 3/31/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x The in car emergency bell shall be operational with 110v source removed. 3/31/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x The building is in the process of adding smoke detectors to the elevator and testing will be required when complete. Elevator not red tagged. 3/31/2022
MO Minimum : Elevators (I) - Pits (I)3 Counterweight guards shall extend from a point not more than 12" above the pit floor to a point not less than 7' above the pit floor.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods The walk-in pit door shall be self-closing.