Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 4.5 - Access to Hoistway 8.6.4.14 Hoistway Access Switches x Hoistway access not working properly. Take corrective action and re-test.
A17.1-2016 : Elevators 3.22 - Wire rope fastening and hitch plate 2.20.9.5 Wedge Rope Sockets 2.20.9.5.4 - Hoist rope tail retaining clips shall be properly spaced. 9/12/2024
A17.1-2016 : Elevators 3.22 - Wire rope fastening and hitch plate 2.20.9.7.2 Seizing of Rope Ends 2.20.9.7.2 - Suspension rope tail ends shall be properly seized/banded. They are currently wrapped in electrical tape. 9/12/2024
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.2 On-Site Documentation A code compliant MCP and all the on-site documentation required shall be provided in the machine room. Logs are mostly blank. Need all documentation from 2022 & 2023. 9/12/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts Adjust upthrust roller bearings for proper clearance to door hanger track (multiple floors). 9/12/2024