Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 4.5 - Access to Hoistway 8.6.4.14 Hoistway Access Switches Yes No Hoistway access not working properly. Take corrective action and re-test. 12/8/2025
A17.1-2016 : Elevators 1.17 - Standby power operation 8.10.2.2.1(q) Yes No Elevators that are equipped to operate on Emergency Power shall be tested operating on Em Power, Annually.
A17.1-2016 : Elevators 5.2 - Bottom clearance, runby, and minimum refuge space 8.6.4.11 Runby (Re-Inspect) Yes No Counterweight runby does not meet Code Minimum of 6".
MO Minimum : Elevators (H) - Machine Rooms (H)8 No No 4x4 electrical box used for Fire Alarm Relays,in machine room, shall to have wiring inside the box and cover installed.
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.11.1 Firefighters’ Emergency Operation Documentation No No MCP - Fire Service must be tested and properly documented monthly on Log Sheet
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.2 On-Site Documentation No No A code compliant MCP and all the on-site documentation required shall be provided in the machine room. Logs are mostly blank. Need all documentation from 2022 & 2023. 9/12/2024
A17.1-2016 : Elevators 3.22 - Wire rope fastening and hitch plate 2.20.9.7.2 Seizing of Rope Ends No No 2.20.9.7.2 - Suspension rope tail ends shall be properly seized/banded. They are currently wrapped in electrical tape. 9/12/2024
A17.1-2016 : Elevators 3.22 - Wire rope fastening and hitch plate 2.20.9.5 Wedge Rope Sockets No No 2.20.9.5.4 - Hoist rope tail retaining clips shall be properly spaced. 9/12/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts No No Adjust upthrust roller bearings for proper clearance to door hanger track (multiple floors). 9/12/2024