A17.1-2016 : Elevators
|
5.2 - Bottom clearance, runby, and minimum refuge space
|
2.4.2
|
Yes
|
No
|
Counterweight runby does not meet Code Minimum of 6".
|
|
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.10.2.2.1(q)
|
Yes
|
No
|
Elevators that are equipped to operate on Emergency Power shall be tested operating on Em Power, Annually.
|
|
|
A17.1-2016 : Elevators
|
2.4 - Machine space
|
8.11.2.1.2(g)
|
No
|
No
|
Non-elevator related items shall not be stored in Machine Room.
|
|
|
A17.1-2016 : Elevators
|
2.7 - Fire Extinguisher
|
8.6.1.6.5
|
No
|
No
|
achine Room shall have proper Fire Extinguisher and shall have current monthly/annual test tag.
|
|
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
8.6.11.1 Firefighters’ Emergency Operation Documentation
|
No
|
No
|
MCP - Fire Service must be tested and properly documented monthly on Log Sheet
|
|
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
8.6.4.19.15 Emergency Communications
|
Yes
|
No
|
2-WAY COMMUNICATION DEVICE SHALL WORK..Voice works, Camera does not work.
|
|
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
2.27.1.1.6 Verification of Telephone Operability
|
Yes
|
No
|
Emergency communications loss monitor shall work.
|
2/22/2024
|
|
A17.1-2016 : Elevators
|
3.22 - Wire rope fastening and hitch plate
|
2.20.9.5 Wedge Rope Sockets
|
No
|
No
|
2.20.9.5.4 - Hoist rope tail retaining clips shall be properly spaced.
|
9/12/2024
|
|
A17.1-2016 : Elevators
|
3.22 - Wire rope fastening and hitch plate
|
2.20.9.7.2 Seizing of Rope Ends
|
No
|
No
|
2.20.9.7.2 - Suspension rope tail ends shall be properly seized/banded. They are currently wrapped in electrical tape.
|
9/12/2024
|
|
A17.1-2016 : Elevators
|
3.28 - Counterweight and counterweight buffer
|
2.21
|
No
|
No
|
2.21.1.2 - Counterweight hold down clamps need to be set properly. They are currently 3"- 4" above weight stack.
|
9/12/2024
|
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.2.2 On-Site Documentation
|
No
|
No
|
A code compliant MCP and all the on-site documentation required shall be provided in the machine room. Logs are mostly blank. Need all documentation for 2022 & 2023.
|
9/12/2024
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.2.1 Repair Parts
|
No
|
No
|
Adjust upthrust roller bearings for proper clearance to door hanger track (multiple floors).
|
9/12/2024
|
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
Yes
|
No
|
Emergency phone is not working. Take corrective action and re-test.
|
12/8/2025
|