Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.6.4.19.15 Emergency Communications Yes No 2-WAY COMMUNICATION DEVICE SHALL WORK..Voice works, Camera does not work.
A17.1-2016 : Elevators 3.22 - Wire rope fastening and hitch plate 2.20.9.5 Wedge Rope Sockets No No 2.20.9.5.4 - Hoist rope tail retaining clips shall be properly spaced. 9/12/2024
A17.1-2016 : Elevators 3.22 - Wire rope fastening and hitch plate 2.20.9.7.2 Seizing of Rope Ends No No 2.20.9.7.2 - Suspension rope tail ends shall be properly seized/banded. They are currently wrapped in electrical tape. 9/12/2024
A17.1-2016 : Elevators 3.28 - Counterweight and counterweight buffer 2.21 No No 2.21.1.2 - Counterweight hold down clamps need to be set properly. They are currently 3"- 4" above weight stack. 9/12/2024
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.2 On-Site Documentation No No A code compliant MCP and all the on-site documentation required shall be provided in the machine room. Logs are mostly blank. Need all documentation for 2022 & 2023. 9/12/2024
A17.1-2016 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 No No achine Room shall have proper Fire Extinguisher and shall have current monthly/annual test tag.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts No No Adjust upthrust roller bearings for proper clearance to door hanger track (multiple floors). 9/12/2024
A17.1-2016 : Elevators 5.2 - Bottom clearance, runby, and minimum refuge space 2.4.2 Yes No Counterweight runby does not meet Code Minimum of 6".
A17.1-2016 : Elevators 1.17 - Standby power operation 8.10.2.2.1(q) Yes No Elevators that are equipped to operate on Emergency Power shall be tested operating on Em Power, Annually.
A17.1-2016 : Elevators 1.6 - Car emergency signal 2.27.1.1.6 Verification of Telephone Operability Yes No Emergency communications loss monitor shall work. 2/22/2024
A17.1-2016 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Emergency phone is not working. Take corrective action and re-test. 12/8/2025
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.11.1 Firefighters’ Emergency Operation Documentation No No MCP - Fire Service must be tested and properly documented monthly on Log Sheet
A17.1-2016 : Elevators 2.4 - Machine space 8.11.2.1.2(g) No No Non-elevator related items shall not be stored in Machine Room.