A17.1-2016 : Elevators
|
1.12 - Car enclosure
|
2.14
|
No
|
No
|
Car Door strike-jamb is damaged, resulting in an open hole leading to the underside of the car of approx 1" by 5".
|
|
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.11.2.1.1(q)
|
Yes
|
No
|
Elevators that are equipped to operate on Emergency Power shall be tested operating on Em Power, Annually.
|
|
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
2.27.1.1.6 Verification of Telephone Operability
|
Yes
|
No
|
Emergency communication loss monitor shall work.
|
2/22/2024
|
|
A17.1-2016 : Elevators
|
2.4 - Machine space
|
2.7.1
|
No
|
No
|
MACHINE ROOM - Smoke/Fire Penetrations to be sealed with approved material. Above door is a large hole, from which insulation is falling onto the A/C unit and floor.
|
|
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.2.2 On-Site Documentation
|
No
|
No
|
A code compliant MCP and all the on-site documentation required shall be provided in the machine room. Logs are mostly blank. Need all documentation for 2022 & 2023.
|
9/12/2024
|
|
A17.1-2016 : Elevators
|
3.22 - Wire rope fastening and hitch plate
|
2.20.9.7.2 Seizing of Rope Ends
|
No
|
No
|
2.20.9.7.2 - Suspension rope tail ends shall be properly seized/banded. They are currently wrapped in electrical tape.
|
9/12/2024
|
|
A17.1-2016 : Elevators
|
3.22 - Wire rope fastening and hitch plate
|
2.20.9.5 Wedge Rope Sockets
|
No
|
No
|
2.20.9.5.4 - Hoist rope tail retaining clips shall be properly spaced.
|
9/12/2024
|
|
A17.1-2016 : Elevators
|
5.2 - Bottom clearance, runby, and minimum refuge space
|
2.4.2
|
Yes
|
No
|
Counterweight runby does not meet Code Minimum of 6".
|
|
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
8.6.11.1 Firefighters’ Emergency Operation Documentation
|
No
|
No
|
MCP - Fire Service must be tested and properly documented monthly on Log Sheet
|
|