Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 3.22 - Wire rope fastening and hitch plate 2.20.9.5 Wedge Rope Sockets No No 2.20.9.5.4 - Hoist rope tail retaining clips shall be properly spaced. 9/12/2024
A17.1-2016 : Elevators 3.22 - Wire rope fastening and hitch plate 2.20.9.7.2 Seizing of Rope Ends No No 2.20.9.7.2 - Suspension rope tail ends shall be properly seized/banded. They are currently wrapped in electrical tape. 9/12/2024
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.2 On-Site Documentation No No A code compliant MCP and all the on-site documentation required shall be provided in the machine room. Logs are mostly blank. Need all documentation for 2022 & 2023. 9/12/2024
A17.1-2016 : Elevators 1.12 - Car enclosure 2.14 No No Car Door strike-jamb is damaged, resulting in an open hole leading to the underside of the car of approx 1" by 5".
A17.1-2016 : Elevators 5.2 - Bottom clearance, runby, and minimum refuge space 2.4.2 Yes No Counterweight runby does not meet Code Minimum of 6".
A17.1-2016 : Elevators 1.17 - Standby power operation 8.11.2.1.1(q) Yes No Elevators that are equipped to operate on Emergency Power shall be tested operating on Em Power, Annually.
A17.1-2016 : Elevators 1.6 - Car emergency signal 2.27.1.1.6 Verification of Telephone Operability Yes No Emergency communication loss monitor shall work. 2/22/2024
A17.1-2016 : Elevators 2.4 - Machine space 2.7.1 No No MACHINE ROOM - Smoke/Fire Penetrations to be sealed with approved material. Above door is a large hole, from which insulation is falling onto the A/C unit and floor.
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.11.1 Firefighters’ Emergency Operation Documentation No No MCP - Fire Service must be tested and properly documented monthly on Log Sheet