Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Testing of the relief valve has not been completed. There is no port for the gauge to be connected. Reinspect within 14 days 4/29/2025
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2.5 Sump Pump Required/Capacity (Re-Inspect) x Elevator pit appears to not have a working sumo pump. There is at least 1 foot of water in the pit. Pit shall be kept clean and dry 4/29/2025
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log Fire service shall be tested monthly and recorded on log in machine room.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts Rail bracket at top floor needs to be welded to mounting beam, it was missing.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts Need permanent test connection installed on control valve.